Home › Products › Coaxial heat exchangers
Tube-in-tube · 1–20 HP

Coaxial (tube-in-tube) heat exchangers

A copper inner tube carrying refrigerant inside a steel outer tube carrying water. Short heat path, fast response, small footprint — the standard choice for air-source heat pumps and evaporative chillers in the 1–20 HP range.

Request a quote See specifications
Coaxial heat exchanger, copper inner tube and steel outer tube

Specifications

Standard range below. Non-standard sizes are built to drawing.

Capacity1–20 HP per unit (larger systems use multiple units in parallel)
ConstructionCopper inner tube, steel outer tube (coaxial)
Common modelsSJL5P3832 · SJL10P3832C · SJL15P · SJL20P3832
Refrigerant sideInner copper tube
Water sideOuter steel tube
ConnectionsBrazed or threaded, orientation to customer drawing
CustomisationBuilt to drawing, or reverse-engineered from a sample part
Sample lead time1 day for standard sizes
Production lead time3–10 days for custom units; stock sizes ship immediately
TestingRefrigerant-side pressure test + water-side pressure test + immersion leak test, every unit

Why coaxial

Fast response

Refrigerant and water flow in opposite directions through a short path, so the unit reaches temperature quickly.

Compact

The tubes nest inside each other, which leaves more room for the rest of the unit.

Freeze tolerance

The tube wall has room to deform if water freezes, which reduces the risk of a split compared with rigid assemblies.

Low refrigerant charge

Small internal volume means less refrigerant in the circuit.

Typical applications

Air-source heat pumps

Domestic and commercial hot water and heating units, 5–20 HP.

Evaporative chillers

Condenser-side exchange where water volume is high and response speed matters.

Water-source heat pumps

Source-side exchange with a steel outer tube for durability.

Dryers and process units

Continuous-duty units that need stable exchange and easy servicing.

How we build and test it

1. Tube forming

Copper and steel tubes cut and formed to the drawing.

2. Oxygen-fuel brazing

Both connections brazed and inspected one by one. We do not use TIG welding on these joints.

3. Dual pressure test

Refrigerant side and water side are pressurised and held separately.

4. Immersion leak test

The finished unit goes into water; any continuous bubble stream is a reject.

Custom work: what we need from you

DrawingPDF or CAD, with overall length, connection diameter and mounting hole spacing.
Or a sample partPhotos of both faces and the side, with a ruler in frame.
Three dimensionsOverall length, connection diameter, mounting hole spacing.
Operating dataCapacity in HP, refrigerant type, heating-only or reverse-cycle, water quality.

FAQ

Can you build to our drawing?

Yes. Most of our work is drawing-based. Send the drawing or a sample part and we will confirm feasibility, price and lead time.

What is the minimum order quantity?

There is no fixed minimum for standard sizes; small custom batches are accepted. Tooling is generally not required for coaxial units.

How do you guarantee the joints do not leak?

Every unit is pressure-tested on both circuits and then immersion-tested. We can supply test records with the shipment.

Do you supply to OEM brands outside China?

Yes. We manufacture under customer brand and ship to the customer's forwarder or directly to their factory.

What information do you need for a quotation?

Capacity in HP, refrigerant type, connection sizes, drawing or sample dimensions, and the quantity you expect per order.

Send a drawing, get a quote

Include capacity, refrigerant type and three key dimensions. We reply with specification, lead time and price.

Contact sales